Sign In | Join Free | My burrillandco.com
Home > Triconex DCS >

3708E Invensys Triconex Isolated Thermocouple Module

Joyoung International Trading Co.,Ltd
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now
    Buy cheap 3708E Invensys Triconex Isolated Thermocouple Module from wholesalers
     
    Buy cheap 3708E Invensys Triconex Isolated Thermocouple Module from wholesalers
    • Buy cheap 3708E Invensys Triconex Isolated Thermocouple Module from wholesalers

    3708E Invensys Triconex Isolated Thermocouple Module

    Ask Lasest Price
    Brand Name : Invensys Triconex
    Model Number : 3708E
    Certification : COC
    Price : inquiry
    Payment Terms : T/T
    Supply Ability : 10 Piece per a day
    Delivery Time : 5-8 work days
    • Product Details
    • Company Profile

    3708E Invensys Triconex Isolated Thermocouple Module

    3708E Invensys Triconex Isolated Thermocouple Module


    Product Details:


    Brand NameInvensys Triconex
    Model3708E
    CatalogTMR architecture
    OriginUnited States (USA)
    Dimension16*16*12cm
    Weight1kg
    HS Code8537101190
    PaymentT/T
    Sales Price$4000
    Warranty12 months
    Lead time3-5 work days


    Description:


    A thermocouple input (TC) module includes three independent input channels. Each input channel receives variable voltage signals from each point, performs thermocouple linearization and cold-junction compensation, and converts the result to degrees Celsius or Fahrenheit. Each channel then transmits 16-bit signed integers representing 0.125 degrees per count to the three main processors on demand. In TMR mode, a value is then selected using a mid-value selection algorithm to ensure correct data for every scan.


    Each thermocouple input module is programmable to support one thermocouple type, selected from J, K and T for standard thermocouple input
    modules and from J, K, T and E for isolated thermocouple input modules.


    The isolated module allows users to select upscale or downscale burnout detection with the TriStation software.


    For non-isolated modules, upscale or downscale burnout detection depends on the field termination selected. Triplicated temperature transducers
    residing on the field termination panel support cold-junction compensation.


    Each channel of a thermocouple input module performs auto-calibration using internal precision voltage references. On the isolated module, a faulting coldjunction transducer is annunciated by a cold-junction indicator on the front panel.