| Sign In | Join Free | My burrillandco.com | 
 | 
| Ask Lasest Price | |
| Brand Name : | B&R | 
| Model Number : | X20DOF322 | 
| Certification : | COC | 
| Price : | USD | 
| Payment Terms : | T/T | 
| Supply Ability : | 10EA | 
| Delivery Time : | 3-5 DAYS | 
The module is equipped with 16 outputs for 1-wire connections. The module is designed for source output wiring.
| I/O module | 16 digital outputs 24 VDC for 1-wire connections | 
| B&R ID code | 0xC0EA | 
| Status indicators | I/O function per channel, operating state, module status | 
| Diagnostics | |
| Module run/error | Yes, using LED status indicator and software | 
| Outputs | Yes, using LED status indicator and software (output error status) | 
| Power consumption | |
| Bus | 0.28 W | 
| Internal I/O | 0.95 W | 
| Additional power dissipation caused by actuators (resistive) [W] | +0.56 W | 
| Certifications | |
| CE | Yes | 
| UKCA | Yes | 
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X | 
| UL | cULus E115267 Industrial control equipment | 
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 | 
| DNV | Temperature: B(0 - 55°C) Humidity: B(up to 100%) Vibration: B(4 g) EMC: B(bridge and open deck) | 
| LR | ENV1 | 
| KR | Yes | 
| ABS | Yes | 
| EAC | Yes | 
| KC | Yes | 
| Variant | Current-sourcing FET | 
| Nominal voltage | 24 VDC | 
| Switching voltage | 24 VDC -15% / +20% | 
| Nominal output current | 0.5 A | 
| Total nominal current | 8 A | 
| Connection type | 1-wire connections | 
| Output circuit | Source | 
| Output protection | Thermal shutdown in the event of overcurrent or short circuit (see
value "Short-circuit peak current") Internal freewheeling diode for switching inductive loads (see section "Switching inductive loads") | 
| Diagnostic status | Output monitoring with 10 ms delay | 
| Leakage current when the output is switched off | 5 µA | 
| RDS(on) | 140 mΩ | 
| Peak short-circuit current | <3 A | 
| Switch-on in the event of overload shutdown or short-circuit shutdown | Approx. 10 ms (depends on the module temperature) | 
| Switching delay | |
| 0 → 1 | <300 µs | 
| 1 → 0 | <300 µs | 
| Switching frequency | |
| Resistive load | Max. 500 Hz | 
| Inductive load | See section "Switching inductive loads". | 
| Braking voltage when switching off inductive loads | Typ. 45 VDC | 
| Insulation voltage between channel and bus | 500 Veff | 
| Electrical isolation | Channel isolated from bus Channel not isolated from channel and I/O power supply | 
| Mounting orientation | |
| Horizontal | Yes | 
| Vertical | Yes | 
| Installation elevation above sea level | |
| 0 to 2000 m | No limitation | 
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m | 
| Degree of protection per EN 60529 | IP20 | 
| Temperature | |
| Operation | |
| Horizontal mounting orientation | -25 to 60°C | 
| Vertical mounting orientation | -25 to 50°C | 
| Derating | See section "Derating". | 
| Storage | -40 to 85°C | 
| Transport | -40 to 85°C | 
| Relative humidity | |
| Operation | 5 to 95%, non-condensing | 
| Storage | 5 to 95%, non-condensing | 
| Transport | 5 to 95%, non-condensing | 
| Note | Order 1x terminal block X20TB1F separately. Order 1x bus module X20BM11 separately. | 
| Pitch | 12.5+0.2mm | 

|   | 
 
                                 
                                 
                                 
                                