| Sign In | Join Free | My burrillandco.com | 
 | 
| Ask Lasest Price | |
| Brand Name : | B&R | 
| Model Number : | X20AO4622 | 
| Certification : | COC | 
| Price : | USD | 
| Payment Terms : | T/T | 
| Supply Ability : | 10EA | 
| Delivery Time : | 3-5 DAYS | 


X20AO4622
X20 analog output module, 4 outputs, 10 V or 0 to 20 mA / 4 to 20 mA, 13-bit converter resolution
| B&R ID code | 0x1BA3 | 
| Status indicators | I/O function per channel, operating state, module status | 
| Diagnostics | |
| Module run/error | Yes, using LED status indicator and software | 
| Channel type | Yes, using software | 
| Power consumption | |
| Bus | 0.01 W | 
| Internal I/O | 1.8 W (Rev. ≥ J0), 2.2 W (Rev. < J0) | 
| Additional power dissipation caused by actuators (resistive) [W] | - | 
| Certifications | |
| CE | Yes | 
| UKCA | Yes | 
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X | 
| UL | cULus E115267 Industrial control equipment | 
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 | 
| DNV | Temperature: B(0 - 55°C) Humidity: B(up to 100%) Vibration: B(4 g) EMC: B(bridge and open deck) | 
| LR | ENV1 | 
| KR | Yes | 
| ABS | Yes | 
| EAC | Yes | 
| KC | Yes | 
| Output | ±10 V or 0 to 20 mA / 4 to 20 mA, via different terminals | 
| Max. output current | 10 mA at voltage >5 V 15 mA at voltage <5 V | 
| Digital converter resolution | |
| Voltage | ±12-bit | 
| Current | 12-bit | 
| Conversion time | 300 µs for all outputs | 
| Settling time on output change over entire range | 500 µs | 
| Switch on/off behavior | Internal enable relay for startup | 
| Max. error | |
| Voltage | |
| Gain | 0.08% | 
| Offset | 0.05% | 
| Current | |
| Gain | 0.09% | 
| Offset | 0.05% | 
| Output protection | Short-circuit proof | 
| Output format | |
| Voltage | INT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV | 
| Current | INT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA | 
| Load per channel | |
| Voltage | Max. ±10 mA, load ≥1 kΩ | 
| Current | Load max. 600 Ω (Rev. ≥ J0), 500 Ω (Rev. < J0) | 
| Short-circuit proof | Current limiting ±40 mA | 
| Output filter | First-order low-pass filter / cutoff frequency 10 kHz | 
| Max. gain drift | |
| Voltage | 0.015%/°C | 
| Current | 0.02 %/°C | 
| Max. offset drift | |
| Voltage | 0.032%/°C | 
| Current | 0.032%/°C | 
| Error caused by load change | |
| Voltage | Max. 0.11%, from 10 MΩ → 1 kΩ, resistive | 
| Current | Max. 0.5%, from 1 Ω → 600 Ω, resistive | 
| Nonlinearity | <0.007% | 
| Insulation voltage between channel and bus | 500 Veff | 
| Electrical isolation | Channel isolated from bus Channel not isolated from channel | 
| Mounting orientation | |
| Horizontal | Yes | 
| Vertical | Yes | 
| Installation elevation above sea level | |
| 0 to 2000 m | No limitation | 
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m | 
| Degree of protection per EN 60529 | IP20 | 
| Temperature | |
| Operation | |
| Horizontal mounting orientation | -25 to 60°C (Rev. ≥ J0), 0 to 55°C (Rev. < J0) | 
| Vertical mounting orientation | -25 to 50°C (Rev. ≥ J0), 0 to 50°C (Rev. < J0) | 
| Derating | See section "Derating". | 
| Storage | -40 to 85°C | 
| Transport | -40 to 85°C | 
| Relative humidity | |
| Operation | 5 to 95%, non-condensing | 
| Storage | 5 to 95%, non-condensing | 
| Transport | 5 to 95%, non-condensing | 
| Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. | 
| Pitch | 12.5+0.2mm | 
|   | 
 
                                 
                                 
                                 
                                