MATERIAL NUMBER:
X20BC0083
The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler.
POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed

| B&R ID code | 0x1F1E | 
| Status indicators | Module status, bus function | 
| Diagnostics | |
| Module status | Yes, using LED status indicator and software | 
| Bus function | Yes, using LED status indicator and software | 
| Power consumption | |
| Bus | 2 W | 
| Additional power dissipation caused by actuators (resistive) [W] | - | 
| Certifications | |
| CE | Yes | 
| UKCA | Yes | 
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X | 
| UL | cULus E115267 Industrial control equipment | 
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 | 
| DNV | Temperature: B(0 - 55°C) Humidity: B(up to 100%) Vibration: B(4 g) EMC: B(bridge and open deck) | 
| LR | ENV1 | 
| KR | Yes | 
| ABS | Yes | 
| EAC | Yes | 
| KC | Yes | 
| Fieldbus | POWERLINK (V1/V2) controlled node | 
| Type | Type 2 | 
| Variant | 2x shielded RJ45 (hub) | 
| Line length | Max. 100 m between 2 stations (segment length) | 
| Transfer rate | 100 Mbit/s | 
| Transfer | |
| Physical layer | 100BASE-TX | 
| Half-duplex | Yes | 
| Full-duplex | No | 
| Autonegotiation | Yes | 
| Auto-MDI/MDIX | Yes | 
| Hub propagation delay | 0.96 to 1 µs | 
| Min. cycle time | |
| Fieldbus | 200 μs | 
| X2X Link | 200 μs | 
| Synchronization between bus systems possible | Yes | 
| Electrical isolation | POWERLINK isolated from bus and I/O | 
| Mounting orientation | |
| Horizontal | Yes | 
| Vertical | Yes | 
| Installation elevation above sea level | |
| 0 to 2000 m | No limitation | 
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m | 
| Degree of protection per EN 60529 | IP20 | 
| Temperature | |
| Operation | |
| Horizontal mounting orientation | -25 to 60°C | 
| Vertical mounting orientation | -25 to 50°C | 
| Derating | - | 
| Storage | -40 to 85°C | 
| Transport | -40 to 85°C | 
| Relative humidity | |
| Operation | 5 to 95%, non-condensing | 
| Storage | 5 to 95%, non-condensing | 
| Transport | 5 to 95%, non-condensing | 
| Note | Order 1x terminal block X20TB12 separately. Order 1x power supply module X20PS9400 or X20PS9402 separately. Order 1x bus base X20BB80 separately. | 
| Pitch | 37.5+0.2mm | 
|   | 
 
                                 
                                 
                                 
                                